Solar heating system to replace electric immersion heaters for hot water
|
|
|
Solar water collectors fixed in portrait style to gable hipped end of new pitched roof. Photovoltaic modules fixed landscape style above solar water collectors to gable hipped end of new pitched roof. |
|
|
| Solar buffer tank for domestic hot water, 200-litre capacity indirect open vented cooper storage cylinders. |
|
|
| The photo shows the insulated flow and return pipe work, and (red) solar anti freeze expansion vessel. This allows for the displacement of anti-freeze during normal operation and to accommodate anti-freeze under high temperature conditions. |
Primary heating to the solar buffer tanks located in the roof void. The Solar Collectors are located on the southern gable of the new-pitched roof. The buffer tanks supply back up hot water to the top floor 8 flats in lieu of electrical immersion heater.
| Type: | Flat Plate |
| Size: | 2.07m x 1.12m x 1.09m |
| Quantity: | 7 |
| Working Pressure: | 4.5 bar |
| Flow rate: | 0.02kg/s/m² |
| Orientation: | South facing |
| Primary pump for solar circuit: | |
| Duty: | 0.28kg/s @ 20 kPa |
| System working pressure: | 4.5Bar |
| Static height: | 2.5m |
| Electrical supply: | single phase/ 240volt |
| Max. flow temperature: | 90o C |
Supplier of technology:
BATEC A/S
Danmarksvej 8
DK-4681 Herfølge
Phone: +45 5627 5050
e-mail: admin@batec.dk
www.batec.dk
Photovoltaic system:
A Photovoltaic array supplied by the Intersolar Group is located on the south
elevation of the main roof. The PV modules have a minimum output of 200 watts
peak (wp) with the area of 4 m².
The PV system is complete with an inverter for connection with the low voltage
ac supply 240 vac at 50 H2, and an ammeter and kW hour meter, which is monitored
by means of the BEMS system.
Supplier of technology:
Intersolar Group
Intersolar Ltd
Cock Lane
High Wycombe
Bucks
HP13 7DE
Phone: +44-1494452941